Operations on Scrapers assembly with RAMTRON drive
For relative movements, the positive steps (by Technosoft Software, Manual-Controller Labview, or Low-Level Devil) the Scraper must enter the chamber.
...
Solaris Version | Linux Version |
---|---|
built number 20141222 | built number 20200624_rc |
New features: [ 1 ] "Ctrl On" function [ 2 ] "By-Pass" function [ 3 ] "Init" procedures [ 4 ] "Bad communication" indicator |
...
Enter the value and press "IN" or "OUT" in the desired direction
Single-axis homing
The "Home" button is positioned in the Advanced Display as shown in the figure.
...
of the counter (Position [mm]), and of the setting field.
If the procedure is not successful, that is:
1. hourglass (clessidra) removed
2. encoder value is not zero
3. "End Run OUT" in the OFF state
the system warns with an error detectable by the log.
This procedure can be repeated, unless an "overcurrent" state occurs, due to the motor malfunction.
Warning, this procedure misaligns the values written on DBFile relating to the home position of the resistive encoder (absolute),
causing a relative misalignment between the "Position" and "Absolute Position" values.
IMPORTANT! After this operation, it is recommended to report to the Control Group which will update the configuration files.
...
Otherwise contact the Control Group.
Save, load, and apply configurations
To recover a configuration (it will be inserted in the Saved column [mm])
...
DCS MOV Class
Database record
Satic Static Fork | Dynamic Fork |
---|---|
DCS Commands
...
Key | Value | Comment |
---|---|---|
pathFileTable | /u2/dcs/prefs/MOV/setups | at the moment present on Static DBFile |
MOVClassNumber | 48 | DCS System Class |
serialType | rs232 | Serial device type rs232,rs422,... |
boudRate | 115200 | |
serialSystemType | /dev/ttyS0 | System Resource es. ttyS0,com1,... |
startUpAxisCicleOnOff | yes | At devil start-up put all the axis ON and then OFF |
startUpAxisOn | no | At devil start-up to put all the axis ON |
Technosoft IDM module programming
...