Developer | Version | Release dates | Last update |
---|---|---|---|
2020.2 | 27/08/2020 (DEVIL) 18/02/2021 (First Level Interface) |
|
Subsystem
...
description & Hardware location
This documentation is related to the new DAFNE SIP system with DEVIL Windows and NI COMPAQ DAQ.
Type | Description |
---|---|
Devils (Windows) | 687 |
CPU type (Low-Level demon) | Virtual Machine |
CPU name (Low-Level demon) | vwdantedev02 (192.168.198.160) users: dante, dafne |
Manual Controller (Light Devil style) | 3.0 (stable version), 4.1_rc (release candidate) |
Number of SIP elements (MVC) | 128 |
Racks Location | Rack 089 (Dafne Hall - Ground Flour) Rack 088 (Dafne Hall - Ground Flour) Rack 085 (Dafne Hall - Ground Flour) |
Rack 092 (Dafne Hall - Ground Flour) | |
Front-end Hardware access (NI cDAQ-9189) |
|
Technical Documentation | http://Sharepoint INFN - Gruppo Controlli DA - Controllo SIP Folder |
(devil first run 27/08/2020) |
...
Language | Required Add ons/PlugingsPlugins/Extensions/Libraries |
---|---|
LabVIEW 2019 SP1 1901f3 (64-bit) Windows - Low Level Devil | DCS environment, NI DAQmx |
LabVIEW 7.0 Sun Solaris - High-Level Interface | DCS environment |
...
DCS SIP Class
Database record
Satic Static Fork | Dynamic Fork |
---|---|
ControlTypes references:
| ControlTypes references:
|
sample of one laboratory element: *======================================================* | sample of one laboratory element: *======================================================* |
...
A | B1 | B2 | Pump type | Polynomial | |
-3.15608 | 1.18997 | 0.03988 | 150 | log P = A+B1 log I+ B2 (log I)^2 | |
-2.46559 | 1.31205 | 0.04945 | 55 | ||
-2.07947 | 1.3501 | 0.0528 | 20 | ||
-3.49247 | 1.04077 | 0.02558 | 200 |
Currently, all SIPs are characterized according to the 150 pump type.
...
Out 1 (Lw res) : 10V correspond to 10mA Out 2 (Hi res) : 10V correspond to 1mA |
For the first configuration of NI cDAQ-9189, check NI cDAQ-9189 Configuration page.
NI cDAQ-9189 | ||
4 x CompaqDAQ Controller (NI cDAQ9189) | 1 x I/O module (NI 9403), for each CompaqDAQ | 3 x ADC module (NI 9205), for each CompaqDAQ |
| Protections : overvoltage, overcurrent, and short-circuit protection | RSE (Referenced Single-Ended) Configuration |
...
Configuration the Firewall of a DEVIL Windows
To ensure the commands sent by the first level of DANTE Control System are received by the DEVIL Windows, we must "switch off" the Firewall:
Settings > Update & Security > Windows Security > Firewall & Network Protection
...
Concerting files
...
from Windows
...
to Unix-like operating system
Code Block |
---|
tr -d '\r' < DEVILXXX.DBXXX > DEVILXXX.DBXXX |
Note: Before issuing the command, check the correct file structure.
Remember: Windows: CR+LF |
!CHAOS Acquisition
The CU that acquire SIP is in production http://chaos-hawebui.lnf.infn.it/chaos_dashboard/index.php and the name of the CU is DAFNE/IMPORT/DAFNE_SIP