Aggiornamento versioni

15/12/2021

versionDEVILs
newOCEM_3.4664, 665, 671, 614, 626, 633
newOCEM_3.3ABANDONED (note: some sub-VIs can still have the "_3.3" version in their names)
newOCEM_3.2652, 655, 647, 650, 659, 672, 683, 682, 696, 697, 695, 692 [!C], 693 [!C], 694 [!C], 691 [!C], 673, 674, 675, 676, 678, 644,627, 635
_ethtutti gli altri DEVILs con classe MG1


Note

Le versioni _newOCEM_3.3 – utilizzate sino al 15/12/2021 sui DEVIL 664 e 665 sulla vldantedev028 – sono state rimpiazzate dalle _newOCEM_3.4.
Di conseguenza la "_newOCEM_3.3" è abbandonata e deprecata
WARNING: alcuni sub-VI possono ancora avere il nome che termina con "_3.3".

Impostazione GMG1Dyn all'avvio del DEVIL

13/12/2021

Il recupero dei valori dinamici da memcached da caricare nella GMG1Dyn all'avvio del DEVIL è svolto nella GMG1Loader_eth.vi dal SubVI 

Code Block
/source_linux/0_classes/MG1/database/GMG1DynRecoverData.vi

Image Added

Per evitare disallineamento fra i set e i readout delle polarità, si cambia il valore recuperato da memcached da "polaritySetting" a "outputPolarity".
Si forza quindi l'ultimo valore di "outputPolarity" salvato su memcached nel "polaritySetting" della dinamica.

Nuova sottoclasse per nuovi alimentatori EEI per Quad., Dip. e Dip. pseudo-pulsato.

Allestimento

Macchina: vldantedev024 (LabVIEW 2012, SP1)
DEVIL:       671
VNC:         192.168.198.124:5971
prefs:        TCP_DCS port = 6345, idleTime = 100 ms

Type

DESIGN NAME

SYSTEM NAME

MAC ADRESS

IP

IP [HEX]

Cavo
+

Cavo
-

RACK

Pulsed Dipole

DP01

DHPTB102

Changelog MG1

PS in test

01-12-2020

Cambiati i PSs sotto test (adesso sono connessi ad un carico e limitati in corrente)
QUATB201 e QUATB202 vengono lasciati accesi

- i DBFiles del DEVIL671 sono esposti e configurati sui quadrupoli QUATB201 e QUATB202

...

Nuova sottoclasse per nuovi alimentatori EEI per Quad., Dip. e Dip. pseudo-pulsato.

Allestimento

Macchina: vldantedev024 (LabVIEW 2012, SP1)
DEVIL:       671
VNC:         192.168.198.124:5971
prefs:        TCP_DCS port = 6345, idleTime = 100 ms
IPTable:    da fare

1606151C0A8BE972019002QUAD02DC QuadrupoleQUATB202D3152C0A8BE981817002

DESIGN NAME

Type

SYSTEM NAME

MAC ADRESS

IP

IP [HEX]

POLARITÀ CAVI

RACK

+

-

DP01

Pulsed Dipole

DHPTB102

00:90:E8:67:18:61

192.168.190.157

C0A8BE9D

1

2

SABTF2-001

DH01

DC Dipole

DHSTB201

00:90:E8:66:74:D2

192.168.190.158

C0A8BE9E

3

4

SABTF2-001

DH02

DC Dipole

DHSTB202

00:90:E8:66:74:DC

192.168.190.159

C0A8BE9F

5

6

SABTF2-003

DC01

DC Dipole

DHSTB203

00:90:E8:63:EB:5B

192.168.190.160

C0A8BEA0

7

8

SABTF2-003

QUAD01

DC Quadrupole

QUATB201

00:90:E8:67:

18:

61

192.168.190.

157

C0A8BE9D

1

2

SABTF2-

001

DC Dipole

DH01

DHSTB201

00:90:E8:66:74:

D2

192.168.190.

158

C0A8BE9E

3

4

SABTF2-

001QUAD03

DC Dipole

DC QuadrupoleDH02

QUATB203DHSTB202

00:90:E8:6366:EB74:6ADC

192.168.190.153159

C0A8BE99C0A8BE9F

165

156

SABTF2-002003QUAD04

DC Dipole

DC QuadrupoleDC01

QUATB204DHSTB203

00:90:E8:6763:16EB:075B

192.168.190.154160

C0A8BE9AC0A8BEA0

147

138

SABTF2-002QUAD05003

DC Quadrupole

QUAD01

QUATB205QUATB201

00:90:E8:6667:7416:D506

192.168.190.155151

C0A8BE9BC0A8BE97

1220

1119

SABTF2-002QUAD06

DC Quadrupole

QUAD02

QUATB202QUATB206

00:90:E8:6766:1874:58D3

192.168.190.156152

C0A8BE9CC0A8BE98

1018

917

SABTF2-002

Link of this table:
https://drive.google.com/open?id=1u7TyK1WsR3w2GasDIqW6S-gNXBDvYNkV

Link of another table with the same information:
https://docs.google.com/spreadsheets/d/1n2rS3Ecr308gLilQp7u6ZMFP828-Q82ixltUHv28k68/edit?usp=sharing

New elemType descriptors

...

DC Quadrupole

QUAD03

QUATB203

00:90:E8:63:EB:6A

192.168.190.153

C0A8BE99

16

15

SABTF2-002

DC Quadrupole

QUAD04

QUATB204

00:90:E8:67:16:07

192.168.190.154

C0A8BE9A

14

13

SABTF2-002

DC Quadrupole

QUAD05

QUATB205

00:90:E8:66:74:D5

192.168.190.155

C0A8BE9B

12

11

SABTF2-002

DC Quadrupole

QUAD06

QUATB206

00:90:E8:67:18:58

192.168.190.156

C0A8BE9C

10

9

SABTF2-002

Link of this table:
https://drive.google.com/open?id=1u7TyK1WsR3w2GasDIqW6S-gNXBDvYNkV

Link of another table with the same information:
https://docs.google.com/spreadsheets/d/1n2rS3Ecr308gLilQp7u6ZMFP828-Q82ixltUHv28k68/edit?usp=sharing

New elemType descriptors

Excerpt from  MG1 class documentation

Excerpt Include
MG1 dataset
MG1 dataset

NOTE (*): byte 1 and byte 3 are decoded by the elemType2InterfaceType VI only for some PS classes:

  • byte 1 is meaningful only for SYS8X00 and serial Modbus
  • byte 3 is meaningful only for E642
  • byte 0 and byte 2 do not depend on "protocol" and are passed through as they are.

Be aware that byte 1 and byte 3 can also be used to discriminate other classes (besides those mentioned above) but, in that case, they have to be interpreted by appropriate code.

Pattern for EEI

byte 3      01 = Type quadrupole DC, 02 = Type dipole DC, 03 = Type dipole pseudo-pulsed
byte 2      00 = bipolar, 01 = unipolar with remote control of polarity change
byte 1       Interface type (unique in this case ?) TO BE DECIDED: maybe the pseudo-pulsed should be different
byte 0      Protocol EEI

Pattern for CAENels NGPS

byte 3      TO BE DECIDED
byte 2      TO BE DECIDED
byte 1       TO BE DECIDED
byte 0      Protocol CAENels NGPS

Ethernet connection

Questi alimentatori si connettono in Ethernet e quindi abbiamo lo stesso problema degli alimentatori Genesys e CAENels Easy Driver.
Anche quì, si usa un canale seriale fake per ogni alimentatore e si mette l'IP nel campo subID2.
P.es.: l'IP 192.168.190.131 si scrive come con 4 HEX come C0A8BE83

...

Sviluppo di Command e Control

...

Si parte dalle versioni _newOCEM_3.3.vi create per i CAENels Easy Driver

...

.3.vi create per i CAENels Easy Driver


Jira
serverINFN Ticketing System
columnIdsissuekey,summary,issuetype,created,updated,assignee,priority,status,resolution
columnskey,summary,type,created,updated,assignee,priority,status,resolution
maximumIssues20
jqlQuerykey = lnfdcs-56
serverId8087fedc-8816-3706-9e66-78f987f39e0c

Modifiche rispetto alle versioni precedenti

-78f987f39e0c

Modifiche rispetto alle versioni precedenti


Note

Le versioni _newOCEM_3.3 – utilizzate sino al 15/12/2021 sui DEVIL 664 e 665 sulla vldantedev028 – sono state rimpiazzate dalle _newOCEM_3.4.
Di conseguenza la "_newOCEM_3.3" è abbandonata e deprecata
WARNING: alcuni sub-VI possono ancora avere il nome che termina con "_3.3".

MG1Ctrl_newOCEM_3.4.vi     EEI in progress, CAENels NGPS beta
MG1Cmd_newOCEM_3.4.vi      EEI in progress, CAENels NGPS beta
initHWMG1_newOCEM_3.4.vi   EEI in progress, CAENels NGPS beta
closeMG1_3.4.vi            EEI in progress, CAENels NGPS ready
.../0_classes/MG1/cmd/exeCmd(MG1)_3.4.vi                       EEI in progress, CAENels NGPS betaNGPS
.../0_classes/MG1/cmd/startCmd-MG1_3.4.vi                      EEI in progress, CAENels NGPS betaNGPS
.../0_classes/MG1/cmd/bypass-MG1_eth_3.3.vi                    EEI ready,  CAENels CAENels NGPS ready
.../0_classes/MG1/cmd/libraries/elemType2InterfaceType_3.3.vi  EEI ready, CAENels NGPS readyCAENels NGPS
.../0_classes/MG1/cmd/libraries/SWTCFinalDataCheckE642_3.3.vi  EEI ready,  CAENels CAENels NGPS ready
.../0_classes/MG1/cmd/libraries/SWTCSeekLastData_3.3.vi        EEI ready,  CAENels CAENels NGPS ready

L'alimentatore EEI pulsato DP01, ha degli stati non previsti nella classe MG1:

...

MODE  send standby/operational            aggiustare tempo di commutazione usando maxCmdExeTime#3.

      MODE <elementName> STBY|OPER

Jira
serverINFN Ticketing System
columnskey,summary,type,created,updated,due,assignee,reporter,priority,status,resolution
serverId8087fedc-8816-3706-9e66-78f987f39e0c
keyLNFDCS-34
keyLNFDCS-34

POLA  unipolarWithRemoteCtl   set polarity

20/05/2022 - Change in POLA Executor for EEI sub-class.
Given that the EEI PSs doesn't directly switch from one polarity to the opposite one, the startCmd code that executes the POLA command has been changed. Now it send the modbus command "go to polarity open" before the actual modbus command "go to polarity X".POLA  unipolarWithRemoteCtl   set polarity

      bipolar                 error: notExecutableCmd

...

      STRG <elementName> 0|1Due to a bug in the PS inner control (see PSET command) , the STRG command is useless. As soon as the set current register is written, the PS starts the ramp without any "start ramp" command.

Jira
serverINFN Ticketing System
columnskey,summary,type,created,updated,due,assignee,reporter,priority,status,resolution
serverId8087fedc-8816-3706-9e66-78f987f39e0c
keyLNFDCS-39

...